Compact FP160 control systems

  • 4 / 8 / 16 control systems
  • Control parameters self-optimised
  • Can be networked to the larger overall system
  • Communication with higher level systems
  • Optional: PROFINET communication to the SIMATIC S7

FP160 temperature controllers offer compact control systems for 4 to 16 control circuits. The systems are always designed for heating and cooling, i.e. apart from the corresponding sensor inputs, double the number of outputs are also available. The control systems are fitted with control systems for communication with higher level systems. The basic FP160 configuration has an RS485 interface through which it is possible to network several control systems to an overall system. The controllers can be connected to higher level systems via an optional Profinet/ Sercos interface.

 

The following versions are available:

4 control circuits

  • 4 x PT100-3/4L inputs
  • 8 x heating/ cooling digital outputs

8 control circuits

  • 8 x PT100 inputs or thermal components
  • 16 x heating/ cooling digital outputs

16 control circuits

  • 16 x PT100-2L inputs or thermal components
  • 32 x heating/ cooling digital outputs

 

 

Your benefits:

  • Compact multi-channel controllers for independent controls
  • Networking several controllers to an overall system possible
  • Short-circuit resistant outputs
  • With the ProfiNet model: Easy to connect the data cable by using two sockets
FP160-CP4L4
FP160-CP4L4E
FP160-Cx08
FP160-Cx08E
FP160-Cx16
Control circuits

4

4

8

8

16

Inputs

4x PT100/4-wire

4x PT100/4-wire

Optionally 8 inputs: PT100, thermocoupke, 0..10V, 4..20mA

optionally 8 inputs: PT100, thermocouple, 0..10V, 4..20mA

Optionally 16 inputs: PT100, thermocouple, 0..10V, 4..20mA

Outputs

8x digital

8x digital

16x digital

16x digital

32x digital

Interfaces

RS485

RS485, PROFINET / Sercos

RS485

RS485, PROFINET / Sercos

RS485

Power supply

24VDC

Temperature range

Pt100 model

T input max. 0,0 .. 500,0°C

Fe-CuNi type J

T input max. 0,0 .. 700,0°C

Temperature resolution

0,1K

Maximum power

Heating/ cooling outputs

80mA
inductive loads (e.g. relays) must be fitted with a freewheeling diode!

Connected load

max. capacity

100nF

Power consumption (24VDC)

100mA
200mA Ethernet-version

Alarm contacts

Load capacity

4A Ethernet-version

max. voltage

230VAC Ethernet-version

Information material

Description
Data file
FP160 Manual